Application of AFPM100/B fire equipment power monitoring system in Baise People's Hospital

The fire equipment power monitoring system is used to monitor the working status of the fire equipment, and can provide an alarm signal when the power supply has overvoltage, undervoltage, overcurrent, and lack of equal faults. This paper briefly describes the composition principle of the fire protection equipment power monitoring system: the fire equipment power monitoring system is used to monitor the power supply working status of the fire equipment, and can issue an alarm signal when the power supply has overvoltage, undervoltage, overcurrent, and lack of equal faults. surveillance system. This paper briefly describes the composition principle of the fire protection equipment power monitoring system, and analyzes the design basis and related specifications of the fire equipment power monitoring system in the application. Finally, through the introduction of the Ankerui fire-fighting equipment power monitoring system in the Baise City People's Hospital project, the realization of the function of the fire-fighting equipment power monitoring system and its significance are expounded.

Key words: fire equipment power supply; monitoring system; AFPM100/B; Baise People's Hospital

0 Overview

Baise City People's Hospital was founded in 1928. It has been renamed by Pusheng Hospital, Baise District Hospital and Baise District People's Hospital. In 2002, Baise City was renamed Baise City People's Hospital. It is a comprehensive tertiary hospital with a large scale, complete equipment and strong technical force. It integrates medical treatment, teaching, scientific research, preventive health care and rehabilitation. The project is a new transitional ward 1# and 2# building of Baise City People's Hospital. Both buildings are four-storey buildings. The first floor to the second floor are mainly wards, the third floor is the ICU, and the fourth floor is the operating room.

The two buildings of the project use a total of 6 AFPM3-2AVs, which are installed on the fire-fighting power supply distribution box of the two buildings; the main equipment of the fire-fighting equipment power monitoring system is installed in the fire control room; the on-site power monitoring module is connected to the fire by the bus. AFPM100/B wall-mounted fire equipment power monitoring host in the total control room. This system can alarm the fire equipment power failure in advance to prevent the fire equipment from being used normally when the fire occurs. Once the fire equipment power monitoring system is put into use, it will effectively reduce the incidence of abnormal use of fire equipment.

Since this project is a hospital project, it belongs to a class of public buildings, and the personnel are relatively dense. In order to ensure that the fire-fighting equipment can be put into operation in the first time after the fire occurs, the loss of life and property caused by the fire is minimized, and the reliable fire-fighting equipment is powered. Critical.

There are several characteristics of fire equipment power supply: low probability of use and long-term idleness, but once it has to be used, it must be able to function. Therefore, always maintain the power supply of fire-fighting equipment.

According to the intelligent management requirements, through the monitoring system consisting of the fire equipment power monitoring module and the monitoring host, the whole process of the fire power supply of the two buildings is continuously monitored, centralizedly controlled and unified.

1 reference standard

In recent years, in order to prevent fire-fighting equipment from being used properly during the fire, the state has successively formulated or revised a number of relevant standard specifications to strengthen the monitoring of fire-fighting equipment. There are:

1.1.GB25506-2010 "General technical requirements for fire control room", in the provisions of 5.7 fire power monitors should meet the following requirements:

a) It should be able to display the working status and fault alarm information of the power supply and backup power of the fire-fighting equipment.

b) It shall be able to transmit the working status and undervoltage alarm information of the power supply and backup power of the fire-fighting equipment to the graphic display device of the fire control room.

1.2.GB 28184-2011 "Fire Equipment Power Monitoring System"

1.3.GB 50116-2013 "Fire Automatic Alarm System Design Specification"

2 system components

The project has access to two communication buses. The AFPM series fire equipment power monitoring detectors installed in the power supply box of the fire protection equipment in the two buildings are directly connected to the wall-mounted background. The AFPM100 fire equipment power monitoring system uses a two-layer structure networking mode of the fire equipment power status monitor + voltage / current sensor. The whole monitoring system is comprehensive in function, safe and reliable, accurate in detection and cost-effective. The system uses RS485 network communication internally and provides Modbus-RTU communication protocol to meet the connection of other standard systems. The above-mentioned set of signals is stable and accurate. Fire equipment power monitoring system.

AFPM100 fire equipment power monitoring system is a computer monitoring and control system independently developed by Ankerui. It is suitable for intelligent buildings, high-rise apartments, hotels, restaurants, commercial buildings, industrial and mining enterprises, national key fire protection. Units and monitoring and management of fire equipment power supplies in petrochemical, cultural and educational health, finance, telecommunications and other fields.

The AFPM100 fire equipment power monitoring system can monitor the power of the fire equipment in real time. By detecting the voltage, current, switch status and other related information of the fire equipment power supply, it can determine whether the fire equipment power supply has open circuit, short circuit, over voltage, under voltage, Fault information such as phase loss, phase error, and overcurrent (overload) are alarmed and recorded. Through the friendly human-computer interaction interface, the status of the power of the monitored equipment is reflected in real time and displayed in a centralized manner, thereby effectively avoiding the critical situation that the fire-fighting equipment cannot work normally due to the power failure during the fire, and the protection of the fire-fighting linkage system is maximized. reliability.

The device has reasonable structure, high reliability, strong function, convenient maintenance, high cost performance, and the system interface is intuitive and easy to use.

The system structure topology is as follows:
China Hardware Business Network
System configuration diagram PZ
China Hardware Business Network
System power supply schematic

3 fire equipment power equipment

3.1, AFPM100 fire equipment power supply background:

The main technical parameters
China Hardware Business Network
power supply

l Main power supply: AC220V 50Hz (allows 85%-110% range change)

l Standby power supply: When the main power supply is low voltage or power failure, maintain the monitoring equipment working time ≥8h

l The monitor provides DC24V power for the connected module (voltage/current signal sensor)

Work system: 24-hour work system

communication method:

Modbus-RTU communication protocol, RS485 half-duplex bus mode, transmission distance of 500m (if it exceeds the transmission distance through the repeater).

Monitoring capacity ≤ 128 points

Operational rating

1 Daily duty class: real-time status monitoring, history query.

2 Monitoring operation level: real-time status monitoring, history query, remote reset of detector.

3 System management level: real-time status monitoring, history query, remote reset of detectors, remote modification of detector parameters, system parameter setting and modification of monitoring equipment, operator addition and deletion.

Environmental conditions

1 Workplace: Fire control room, or installed side by side with fire control console

2 Working environment temperature: -10 ° C ~ +55 ° C

3 Working environment relative humidity: ≤95% no condensation

4 Altitude: ≤2500m

5 Pollution degree: Class III, installation category: Level III

3.2, AFPM100 series instruments

3.2.1. Real-time monitoring of two three-phase voltages;

3.2.2, with overvoltage, undervoltage, phase loss, phase error, overcurrent (only with current detection products) alarm;

3.2.3, provide one or two channels (only monitor two-way three-phase AC voltage products) switch input function, can monitor the switch state; (see module selection for details)

3.2.4. Provide one relay output, which can be connected to the alarm control loop;

3.2.5. With event storage function, the alarm can record the time, type and parameter of the alarm occurrence. According to the alarm record, the situation can be analyzed to provide a basis for eliminating the fault;

3.2.6. Using fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and timely discover the alarm information. The standard MODBUS protocol can be connected to various standard systems via the RS485 interface;

3.2.7, high integration, network, high degree of intelligence, reasonable operating characteristics;

4 system function

4.1, monitoring alarm function

l Monitored device power loop switch status

l Working status of the monitored device power supply (voltage, current and alarm status information)

l Alarm response time: ≤100s

l Alarm sound signal: can be manually eliminated, can be started again when there is alarm signal input again

l Alarm light signal: red LED indicator is always on

4.2, control output function

l Remote control of alarm relays of individual or all monitored devices

l Monitor control output: normally open passive contact, capacity: AC250V 3A or DC30V 3A

4.3, fault alarm function

l The connection between the monitor and the module (voltage/current signal sensor) is open and shorted

l Monitor mains undervoltage (≤80% mains voltage) or overvoltage (≥110% mains voltage)

l The connection between the monitor and its remote power supply is open and shorted.

l When the above fault occurs in the monitor, it can send a sound and light fault alarm signal that is obviously different from the monitoring alarm signal.

l Fault alarm response time: ≤100s

l Fault alarm sound signal: manual elimination, can be started again when there is alarm signal input again

l Fault alarm light signal: yellow LED indicator is always on

l During the fault, the normal operation of the non-faulty loop is not affected.

4.4, self-test function

l Connection check: open circuit and short circuit of communication line and split power line

l Device self-test: manual check or system self-test

l Self-test time: ≤60s

4.5, alarm record function

l Record 10000 related fault alarm information

l Alarm type: fault type, time of occurrence, fault description

l Alarm event query

l Alarm record printing

4.6, printing function

The monitoring system can print Chinese characters and print alarm events and time, fault events and time.

4.7, silence

In the event of an alarm such as an alarm or a fault, the speaker of the monitoring device will give a corresponding alarm sound to prompt, press the “mute” button to terminate the alarm, and the alarm light will be green. During the period, the staff can handle the faults. Everything returned to normal and the alarm light went out. If a new fault occurs, the silence indicator will turn off and the speaker will sound an alarm again.

5 Conclusion

As a kind of pre-alarm system, the fire-fighting equipment power monitoring system has the advantage of alarming the power failure of the fire-fighting equipment in advance to prevent the fire-fighting equipment from being used normally when the fire occurs. Once the fire-fighting equipment power monitoring system is put into use, it will effectively reduce the incidence of abnormal use of fire-fighting equipment, scientific management of the entire building safety, and reduce the risk of fire to the lives and property of personnel in the building. Social and economic benefits.

references

[1]. Ren Zhicheng Zhou Zhong. Principles and Application Guide of Digital Measurement of Electric Power Measurement [M]. Beijing. China Electric Power Press. 2007. 4

About the author: Chen Wei (1989-), female, Jiangsu Ankerui Electric Manufacturing Co., Ltd., technical engineer, the main research direction is intelligent power monitoring and power management system. Technical exchange fax mobile phone QQ home page: http://
China Hardware Business Network Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

Cultured Stone Texture Pu Sandwich Panel

Rich selection of textures and colors meet different decoration requirements, giving the city and the buildings a new look.
The PU foam is the most advanced and eco-friendly insulation material in the world. With the help of the back aluminum foil, the thermal preservation effect achieves the best.
The unique structure prevents the heat loss in winter. Meanwhile it reduces the heat of the summer sunshine.
Aceta paintcoat and flurocarbon paint of weather resistance performance are applied on surface of wall panel. It is reserved with superior self-cleaning, weather resistance, corrosion resistance and acid& alkali resistance performance.
Light weight with 3.7Kgs/m2 makes the installation easy.
The installation process is clean and tidy without any noise and dust, construction waste.
Different selections of accessories meet different effects.
High quality and stable performance: Manufactured in CNC automation production line, the product pass rate can reach 99.9% with stable chemical structure and physical structure.

Cultured Stone Texture PU Sandwich Panel

Metal Siding Panels,Composite Metal Wall Panels,Wall Cladding Panels,Cultured Stone Texture Pu Sandwich Panel

Jinan Zhengtang Insulation Decoration Material Co.Ltd , https://www.ztwallsiding.com